Motor de Búsqueda de Datasheet de Componentes Electrónicos
  Spanish  ▼
ALLDATASHEET.ES

X  

3G5A2-RPT01-E Datasheet(PDF) 96 Page - Omron Electronics LLC

No. de pieza 3G5A2-RPT01-E
Descripción Electrónicos  Programmable Controllers
PDF  182 Pages
Scroll/Zoom Zoom In 100%  Zoom Out
Fabricante Electrónico  OMRON [Omron Electronics LLC]
Página de inicio  http://www.omron.com/index3.html
Logo OMRON - Omron Electronics LLC

3G5A2-RPT01-E Datasheet(HTML) 96 Page - Omron Electronics LLC

Back Button 3G5A2-RPT01-E Datasheet HTML 92Page - Omron Electronics LLC 3G5A2-RPT01-E Datasheet HTML 93Page - Omron Electronics LLC 3G5A2-RPT01-E Datasheet HTML 94Page - Omron Electronics LLC 3G5A2-RPT01-E Datasheet HTML 95Page - Omron Electronics LLC 3G5A2-RPT01-E Datasheet HTML 96Page - Omron Electronics LLC 3G5A2-RPT01-E Datasheet HTML 97Page - Omron Electronics LLC 3G5A2-RPT01-E Datasheet HTML 98Page - Omron Electronics LLC 3G5A2-RPT01-E Datasheet HTML 99Page - Omron Electronics LLC 3G5A2-RPT01-E Datasheet HTML 100Page - Omron Electronics LLC Next Button
Zoom Inzoom in Zoom Outzoom out
 96 / 182 page
background image
83
Fault Check Flowchart
A
C
B
B
A
B
RUN indicator not lit
NO
RUN or
MONITOR
mode?
YES
ERROR indi-
cator lights?
NO
Can Online
mode be set?
YES
NO
WDT indica-
tor lights?
NO
YES
Can Online
mode be set?
YES
NO
WDT indica-
tor lights?
YES
ON
A30600 ON?
OFF
ON
A30601 ON?
OFF
ON
A30602 ON?
OFF
ON
A30603 ON?
OFF
NO
RUN indica-
tor lights?
YES
*When an I/O verifica-
tion error is specified
as a fatal error in the
PC Setup.
**This error does not
occur when disabled
as an error in the PC
Setup.
At this time, it is assumed that the POWER indicator is normally
lit.
(To next page)
YES
NO
START input OFF
Connect peripheral de-
vice and check error
Check word A306
I/O verify error*
SYSMAC BUS terminator
missing
SYSMAC BUS/2 termina-
tor missing**
Close START input termi-
nals of Power Supply Unit
Unit is disconnected. Iden-
tify erroneous Unit by veri-
fying I/O table, mount Unit
correctly, and then create
I/O table
Check terminator and
Slave Rack Power Supply
Unit of SYSMAC BUS
Check terminator and
Slave Rack Power Supply
Unit of SYSMAC BUS/2
End
Replace Unit
Turn power OFF and ON
again
Set RUN or MONITOR
mode
Troubleshooting Flowcharts
Section 5-2



Html Pages

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 98 99 100  ...More


Datasheet Descarga

Go To PDF Page


Enlace URL



¿ALLDATASHEET es útil para Ud.?  [ DONATE ] 

Todo acerca de Alldatasheet   |   Publicidad   |   Contáctenos   |   Política de Privacidad   |   Enlace a la hoja de datos    |   Intercambio de Enlaces   |   Lista de Fabricantes
All Rights Reserved©Alldatasheet.com


Mirror Sites
English : Alldatasheet.com  |   English : Alldatasheet.net  |   Chinese : Alldatasheetcn.com  |   German : Alldatasheetde.com  |   Japanese : Alldatasheet.jp
Russian : Alldatasheetru.com  |   Korean : Alldatasheet.co.kr  |   Spanish : Alldatasheet.es  |   French : Alldatasheet.fr  |   Italian : Alldatasheetit.com
Portuguese : Alldatasheetpt.com  |   Polish : Alldatasheet.pl  |   Vietnamese : Alldatasheet.vn
Indian : Alldatasheet.in  |   Mexican : Alldatasheet.com.mx  |   British : Alldatasheet.co.uk  |   New Zealand : Alldatasheet.co.nz
Family Site : ic2ic.com  |   icmetro.com