M2RTS-S-AB-R2/N
AI

The **M2RTS-S-AB-R2/N** is a specific model within the M2RTS series of **RTD (Resistance Temperature Detector) Transmitters**. These devices are used to convert the small resistance changes from a temperature sensor (like a Pt100) into a standardized industrial signal (like 4-20mA or 0-10V).
---
### 1. Component Breakdown (Model Code Analysis)
The alphanumeric string provides specific details about the internal electronic configuration:
| Segment | Meaning | Specification |
| :--- | :--- | :--- |
| **M2RTS** | Series Name | Compact RTD Transmitter (Plug-in Type) |
| **S** | Output Type | Standard DC output (Current/Voltage) |
| **AB** | Input/Output | **A:** Pt 100 (3-wire) / **B:** 4–20 mA DC |
| **R2** | Power Supply | 100 – 120V AC (Standard utility power) |
| **N** | Option | Standard version (No special coating or options) |
---
### 2. Core Electronic Specifications
This transmitter utilizes several key electronic stages to ensure accuracy and isolation.
* **Input Stage:** Designed for a 3-wire Pt100 RTD. It includes a constant current source to excite the sensor and bridge circuitry to compensate for lead wire resistance.
* **Isolation:** The "R2" model typically features **3-way isolation**. This means the Input, Output, and Power circuits are electrically separated (usually up to 2000V AC), preventing ground loops and protecting the PLC/Controller.
* **A/D and D/A Conversion:** Modern M2RTS units use a microprocessor-based system where the analog resistance is digitized, linearized (to correct for the RTD's non-linear curve), and then converted back to a precise 4-20mA analog output.
---
### 3. Electrical Connections
The unit is typically a plug-in style that fits into a specialized base.
| Terminal No. | Function | Description |
| :--- | :--- | :--- |
| **1 - 2** | Output (+) / (-) | 4-20mA DC Signal to PLC |
| **3 - 4** | Power Supply | 100-120V AC Input |
| **5, 6, 7** | Input (A, B, b) | Connections for the Pt100 RTD |
---
### 4. Technical Performance Constants
* **Accuracy:** Generally $\pm 0.1\%$ of span.
* **Temperature Coefficient:** $\pm 0.015\%$ per degree Celsius.
* **Response Time:** $\leq 0.5$ seconds (0 to 90%).
* **Burnout Protection:** If the RTD wire breaks, the electronics are programmed to drive the output to "Upscale" (over 20mA) to alert the system of a failure.
---
- ⤷
How do I calibrate the Zero and Span on this transmitter?
- ⤷ Can this model be used with a 2-wire RTD instead of a 3-wire?
- ⤷ What is the maximum load resistance for the 4-20mA output?