FLM-CF-R/
AI

The **FLM-CF-R** is an addressable FlashScan® monitor module primarily used in Honeywell/Fire-Lite fire alarm systems. It is specifically designed to provide a supervised interface for dry-contact devices, such as waterflow switches or manual pull stations.
---
### 1. Key Electronic Components & Features
The module acts as a bridge between the Fire Alarm Control Panel (FACP) and initiating devices.
| Feature | Specification |
| :--- | :--- |
| **Communication Protocol** | FlashScan® (High-speed polling) |
| **Operating Voltage** | 15 to 32 VDC (Peak-to-Peak) |
| **Standby Current** | 375 μA (typical) |
| **LED Indicators** | Bi-color LED (Green for polling, Red for alarm) |
| **Address Range** | 01–159 (set via rotary switches) |
| **End-of-Line (EOL) Resistor** | 47K Ohms |
---
### 2. Functional Electronic Design
#### A. Rotary Addressing
The device features two integrated rotary switches (tens and ones). These allow technicians to set a unique decimal address for the module, ensuring the control panel can identify the exact location of a triggered switch.
#### B. Supervisory Circuit
The electronics include a **Class B (Style B)** initiating circuit. It monitors the wiring between the module and the dry contact:
- **Normal:** 47K Ohm resistance detected.
- **Alarm:** Short circuit detected (contact closed).
- **Trouble:** Open circuit detected (wiring break).
#### C. FlashScan® Technology
Unlike older "CLIP" protocols, the FLM-CF-R uses **FlashScan®**, a high-speed communication protocol. This allows the control panel to poll multiple devices simultaneously, significantly reducing the time it takes for an alarm signal to reach the main panel.
---
### 3. Wiring Terminal Configuration
The module typically features a terminal block for field wiring:
| Terminal | Description |
| :--- | :--- |
| **T1 & T2** | SLC (Signaling Line Circuit) Connection |
| **T3 & T4** | Supervised Initiating Device Circuit (Dry Contacts) |
---
### 4. Physical Indicators
The onboard LED is software-controlled by the panel:
- **Blinking Green:** Indicates the module is communicating successfully with the FACP.
- **Steady Red:** Indicates an alarm condition or active state.
- ⤷
What is the difference between Class A and Class B wiring for this module?
- ⤷ How do you reset the FLM-CF-R after an alarm event?
- ⤷ Can this module be used to control NAC circuits?